V. P. Berardi et alii, Frattura ed Integrità Strutturale, 48 (2019) 222-229; DOI: 10.3221/IGF-ESIS.48.23 226 RESULTS AND DISCUSSION he load-displacement curve, acquired by the testing machine during the preliminary debonding experiment (specimen #1), is plotted in Fig. 6, exhibiting a typical trend as in literature. The maximum value of the applied force of about 13 kN was recorded, whereas the maximum displacement ranged within 3 mm. A typical debonding failure mode was observed (Fig. 7), corresponding to the optimal collapse mechanism of strengthened concrete due to the fact that the concrete shear strength is lower than for the adopted resin. Figure 6 : Load-displacement curve. Figure 7 : Debonding failure mode. Figure 8 : GFRP strain vs. time curves. Figure 9 : Tangential slip vs. time curves obtained by DIC technique. The tangential slips δ i,i+1 evaluated by DIC technique, are considered as the relative displacement of mid points between the cross-sections corresponding to i-th and (i+1)-th GFRP strain gauges. The GFRP strain ε i versus time curves and the tangential slip δ i,i+1 versus time curves are plotted in Figs. 8 and 9 respectively. The proposed methodology is capable of 0 2 4 6 8 10 12 14 0 0.5 1 1.5 2 2.5 3 3.5 4 Load [kN] Displacement [mm] 0 0.001 0.002 0.003 0.004 0.005 0 50 100 150 200 250 300 350 Strain [ ] Time [s] Strain Gauge # 0 Strain Gauge # 1 Strain Gauge # 2 Strain Gauge # 3 Strain Gauge # 4 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0 50 100 150 200 250 300 350 Tangential slip [mm] Time [s] T